Shopping security
The HIMA 32102, also cataloged as the 32102 2-fold relay amplifier, operates as a dedicated hardware component for safety-related control systems within HIMA Planar4 platforms.
| Parameter | Specification |
|---|---|
| Model | 32102 |
| Brand | HIMA |
| Origin | Germany |
| Module Type | 2-fold relay amplifier |
| Relay Channels | 2 independent relay outputs |
| Output Type | Floating NO contacts (potential-free) |
| Operating Voltage | 24 VDC / 135 mA |
| Switching Voltage | Up to 250 V AC/DC |
| Switching Current | Up to 4 A (10 mA minimum) |
| Inrush Peak Current | 12 A maximum for 1 s (non-periodic) |
| Response Time | Contact: 10 ms; Signal: 3 ms |
| Reset Time | Contact: 12 ms; Signal: ~8 ms |
| Relay Contact Material | AgNi, gold-plated |
| Operating Temp | -25 to +60 deg C |
| Protection Class | IP20 |
| Power Consumption | 3.24 W maximum |
| Dimensions | Standard Planar4 rack-mount / DIN rail card footprint |
| Weight | 0.25 kg typical |
The 32102 hardware logic satisfies the test criteria for Requirement Class RC 1...7 according to DIN V 19250, achieving compatibility metrics up to SIL4 certification limits. Internal circuitry leverages full electrical galvanic isolation to decouple the 24 VDC logic input drive from the potential-free dual-channel outputs. Configured under a permanent de-energize-to-trip architecture, any interruption of the 24 VDC control loop drops the internal gold-plated AgNi contacts in approximately 12 ms, executing a predictable fail-safe state execution to actuate downstream final elements without logic processing delays.
Q: What are the specific power limitations for inductive loads connected to the 32102 relay contacts at high DC voltages?
A: For DC resistive loads, the contacts sustain up to 120 W at 30 VDC or 40 W at 250 VDC. When switching inductive loads at 250 VDC, external suppression components must be utilized to maintain peak inrush limits below 12 A for 1 s.
Q: Can the 32102 module be hot-swapped while the Planar4 rack is actively under power?
A: No. Online replacement or physical handling of the 32102 module while the system power or the field load loops are energized can cause transient voltage breakdown across the terminal interface and disrupt certified safety paths.
Q: Is a minimum load current required to prevent contact passivation on the output relay channels?
A: Yes. Due to the properties of the gold-plated AgNi contact interfaces, a minimum switching current of 10 mA must be maintained to ensure proper signal continuity through the execution path.